Electrical Pre-heating — Resitherm

Service decoration

Pipe nominal diameter – DN 50 to DN 1000

Maximum pre-heating temperature – 130 °C

Pipe nominal diameter – DN 50 to DN 1000

Maximum pre-heating temperature – 130 °C

Electrical pre-heating provides a simple and rapid method of dry-process pipe pre-stressing.

Construction Cost Savings:

  • minimises the need for conventional expansion compensation elements
  • fewer welds, fittings, couplings and pipe supports
  • fewer excavations and backfills (when replacing U-shaped expansion loops)
  • reduced thermal expansion stress on branch connections
  • lower pumping costs during operation

Electrical Pre-heating Procedure:

  • arrival on site, site handover, health and safety briefing
  • assembly of the pre-heating unit (Resitherm device, power generator, sensors)
  • welding of connection studs to all pipe ends
  • connection of heating cables to the pipeline
  • marking the “zero” position of the pipeline prior to commencement of pre-heating
  • commencement of pre-heating
  • monitoring of thermal expansion and temperature throughout the heating process
  • attainment of target temperature and thermal expansion; handover of the pipeline route for backfilling and compaction
  • disconnection of the equipment upon completion of backfilling and compaction
  • demobilisation, site clean-up, departure from site

The Electrical Pre-heating Technology Enables:

  • thermal pre-heating in locations where no heating medium (hot water) is available
  • pre-stressing of individual pipeline sections to different target temperatures, regardless of any available heating medium temperature
  • pre-stressing of a single pipeline branch, e.g. a process pipeline, independently of the rest of the network
  • flexible sequential pre-stressing of individual pipeline network sections in an order determined by construction progress
  • a more cost-effective solution that is superior both structurally and operationally compared to installation methods using single-acting expansion compensators
  • optimisation of heat distribution networks installed cold — an alternative to the use of U-shaped expansion loops
  • sectional thermal pre-heating (progressive pre-stressing) during the construction of long-distance transmission pipelines
  • installation of selected heat network sections requiring local thermal pre-heating, without the need to complete adjacent or connecting sections first
  • restoration of pre-stress during any repair of heat network pipeline sections, regardless of the original installation method